Megapress Stainless 316
Range
General
Press connector made of stainless steel 1.4404
Marking
Manufacturer, pipe dimension, batch, green dot on press end, green detachable label as press indicator
-
Show more
Press connector with
SC‑Contur
Inadvertently unpressed connections are noticed immediately during a leakage test.
Viega guarantees the detection of unpressed connections in the following pressure ranges with water, compressed air or inert gases:
Min. water pressure: 0.1 MPa / 100 kPa / 1 bar / 14.5 PSI
Max. water pressure: 0.65 MPa / 650 kPa / 6.5 bar / 94.3 PSI
Min. air pressure: 22 hPa / 2.2 kPa / 22 mbar / 0.3 PSI
Max. air pressure: 0.3 MPa / 300 kPa / 3 bar / 43.5 PSI
Sealing elements
EPDM (ethylene propylene diene rubber), black, pre-assembled
Notice
The sealing materials of the press connector system are subject to thermal ageing, which depends on the media temperature and the operating time.
The higher the media temperature, the faster the thermal ageing of the sealing material progresses.
In the case of special operating conditions, e.g. industrial heat recovery systems, it is necessary to compare the specifications of the appliance manufacturer with the specifications of the press connector system.
Before using the press connector system beyond the areas of application described or if in doubt about the correct selection of material, please contact Viega.
Dimensions
D½–4, size availability in accordance with the national regulations
Tools
The functional safety of Viega press connector systems depends primarily on the faultless condition of the press tools used. Viega recommends the use of Viega press tools for pressing Viega press connectors. The Pressgun Press Booster is required for pressingMegapress Stainless 316 XL press connectors. Viega press tools have to be regularly maintained by authorised service partners.
Areas of application
Industrial and plant engineering
Cooling and heating systems
Compressed air systems
Rainwater
Agriculture
Systems for technical gases (request required)
Note
When used for other areas of use and when in doubt about the right selection of material, please contact Viega. The system components should be protected against high concentrations of chloride generated by both the medium and by external factors. Detailed information about applications, restrictions and national standards and directives can be found in the product information, either printed or on the Viega website.
Note – Standards and approvals
Suitable for stainless steel pipes(1 .4541/1.4550/1.4571) according to DIN EN 10216‑5 and DIN EN 10217‑7.
For use in heating systems, observe VDI Regulation 2035 and DIN EN 12828.
Operating conditions
The press connector systemMegapress Stainless 316 can be used with the following operating parameters:
Heating systems in accordance with DIN EN 12828
Operating temperature max. 105 °C / 221 °F
The press connector systemMegapress Stainless 316 is designed for nominal pressure PN 16.
Press connector material
Stainless steel 1.4404(3 16L)
Subject to change without prior notice!
Latest Z- and installation dimensions as well as further technical information can be found on the Viega website and have to be checked before purchase, planning, construction work and use. Our products are continuously optimised.
This product description contains important information on choice of product and system, mounting, commissioning as well as intended use and, if required, on maintenance measures. This information on products, their features and application techniques is based on currently valid standards in Europe (e.g. EN) and/or in Germany (e.g. DIN/DVGW). Some passages in the text may refer to technical regulations in Europe/Germany. These should be considered as recommendations for other countries where no corresponding national requirements exist. The relevant national laws, standards, regulations, directives and other technical provisions take priority over the German/European directives specified in this product description: The information herein is not binding for other countries and regions and should be understood as recommendation.